Capacity Rates: C20, C10 and C5

Battery Testing Methods · Last reviewed 2026-09-16

Direct answer: A battery's measured capacity depends on how fast it is discharged. The rate is written as C20 (the current that drains the battery in 20 hours), C10 (10 hours) or C5 (5 hours). Faster discharge gives a lower measured capacity, so a capacity figure is meaningless without its rate.

The rate ladder

RateDischarge timeMeasured capacityTypical use
C2020 hoursHighest (the quoted Ah)General rating, solar
C1010 hoursLower than C20Industrial / telecom
C55 hoursLower againUPS, high-rate applications

Why faster discharge lowers capacity

At higher currents, more of the stored energy is wasted inside the battery — as heat in the internal resistance and through slower electrochemical access to the active material. A battery that delivers 100 Ah at the gentle C20 rate may deliver only ~85 Ah at C10 and less still at C5. The rate is part of the specification, not a footnote — see capacity testing for the full C20 method.

How to compare two capacity claims

Compare within the same rate: C20 to C20, C10 to C10. A battery quoted at C10 will look smaller than one quoted at C20 even if it is physically similar. The same discipline applies as with CCA standards — the number's basis defines what it means.

The Author's Take

Position: Capacity is not one number — it is a curve over discharge rate, and the single most useful question about any Ah figure is "at what rate?", because the answer changes the number.

Reasoning: The C20 number is the flattering slow rate; real applications discharge faster and get less. A buyer who compares within one rate — and knows the C20/C10/C5 ladder — reads capacity claims the way engineers do.

This is the author's editorial view, not a purchasing guarantee.